Fire-rated walls and floors only work if every pipe, cable and joint through them is sealed with a tested firestop system. BC Building Products now supplies firestop products to mechanical, electrical, drywall, insulation and firestop contractors across the Lower Mainland, from our warehouse at 8241 129 St in Surrey.
We carry the Tremco TREMstop range (acrylic and silicone firestop sealants and sprays, Smoke & Sound sealants, SuperStrip intumescent wrap, Fire Mortar, MP putty pads and FS Blanket), plus the Tremco polyurethane and hybrid sealants listed for fire-resistive joint systems, and Hilti FS-ONE MAX intumescent sealant. Every product links to the manufacturer’s Technical Data Sheet (TDS). Where no public Safety Data Sheet (SDS) link exists, request it from us.
| Product | Type / use | TDS | SDS | Product page |
|---|---|---|---|---|
| TREMstop® Acrylic | Firestop sealant (acrylic latex, gun grade): Through-penetrations in fire-rated walls and floors | TDS | SDS | View |
| TREMstop® Acrylic SP | Firestop spray (acrylic latex): Long fire-rated joints such as head-of-wall and perimeter joints | TDS | SDS | View |
| TREMstop® Fyre-Sil | Firestop sealant (silicone, gun grade): Through-penetrations and fire-rated joints | TDS | SDS | View |
| TREMstop® Fyre-Sil SL | Firestop sealant (silicone, self-levelling): Horizontal (floor) through-penetrations | TDS | SDS | View |
| TREMstop® Smoke & Sound | Smoke & sound sealant (acrylic latex, gun grade): Joints and penetrations in smoke-rated partitions | TDS | On request | View |
| TREMstop® Smoke & Sound SP | Smoke & sound spray (acrylic latex): Long joints in smoke-rated and sound-rated partitions | TDS | On request | View |
| TREMstop® SuperStrip | Intumescent wrap strip: Plastic (combustible) pipe through-penetrations | TDS | On request | View |
| TREMstop® Fire Mortar | Firestop mortar (microsilica): Large openings and annular spaces | TDS | On request | View |
| TREMstop® MP | Firestop putty pad: Metal and plastic electrical boxes in gypsum wall assemblies | TDS | On request | View |
| TREMstop® FS Blanket | Fibre blanket / packing: Floor-to-floor, floor-to-wall, head-of-wall and wall-to-wall joints | TDS | SDS | View |
| Tremco Dymonic® 100 | Polyurethane sealant (firestop-listed systems): Smoke and sound partitions | TDS | On request | View |
| Tremco Dymeric® 240FC | Polyurethane sealant (multi-component, fast cure): Smoke and sound partitions | TDS | On request | View |
| Tremco Vulkem® 45SSL | Polyurethane sealant (self-levelling): Horizontal joints in smoke and sound partitions | TDS | On request | View |
| Tremco Dymonic® FC | Hybrid sealant (fast cure): Smoke and sound partitions | TDS | On request | View |
| Hilti FS-ONE MAX Intumescent Firestop Sealant | Intumescent firestop sealant: Metal, insulated metal and plastic pipe penetrations | TDS | SDS | View |
Start with the tested system for your assembly (concrete, gypsum or wood), the penetrating item (metal pipe, plastic pipe, cable or joint) and the required rating. Then choose the product that system lists. Plastic pipes need intumescent products; long joints often suit a spray; floor openings with many penetrations suit a self-levelling silicone. Our team can help you match products to the systems on your firestop schedule.
We supply Tremco TREMstop firestop products and Hilti FS-ONE MAX intumescent firestop sealant.
No. Firestop products are tested as part of a listed firestop system. The rating belongs to the system: the assembly, the penetrating item, the firestop product and any accessories.
Plastic pipes need an intumescent product, such as Tremco TREMstop SuperStrip wrap or Hilti FS-ONE MAX, installed to a tested system for that pipe and assembly.
Yes. TREMstop Acrylic Spray is sprayable for long fire-rated joint runs.
Each product below links to the manufacturer Technical Data Sheet and Safety Data Sheet.
Send us your firestop schedule or system numbers and quantities. We will price them and confirm stock at our Surrey warehouse.